HomeMy WebLinkAbout43661 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 ORDINANCE NO. 4 3 6 6 AN ORDINANCE OF THE CITY OF AUBURN, WASHINGTON AMENDING SECTION 15.36.035 ENTITLED "SECTION 10.308 AMENDED - AUTOMATIC SPRINKLER SYSTEMS" CONTAINED IN CHAPTER 15.36 ENTITLED "FIRE CODE" BY ADDING AND DELETING CERTAIN LANGUAGE CONTAINED IN SUBSECTIONS 1., 2., 3., 5., 6., 7., 8., 10 AND 11 AND ADDING NEW SUBSECTIONS 12 THROUGH 14 WHICH PROVIDES FOR FIRE SPRINKLER SYSTEMS BASED ON THE OCCUPANCY GROUP AND ASSOCIATED HAZARDS. WHEREAS, the City of Auburn desires to amend Auburn City Code Section 15.36.035 entitled "SECTION 10.308 AMENDED - AUTOMATIC SPRINKLER SYSTEMS" contained in CHAPTER 15.36 entitled "FIRE CODE" by adding and deleting certain language contained therein; NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF AUBURN, WASHINGTON, DO ORDAIN AS FOLLOWS: Section 1. PURPOSE. The purpose of this ordinance is to amend Auburn City Code Section 15.36.035 entitled "SECTION 10.308 AMENDED - AUTOMATIC SPRINKLER SYSTEMS" contained in Chapter 15.36 entitled, "FIRE CODE" by adding and deleting certain language contained in subsections 1., 2., 3., 5., 6., 7., 8., 10 and 11 which provides for the fire sprinkler systems based on the occupancy group and associated hazards and conforms the language to the Uniform Fire Code, 1988 Edition. ------------------- Ordinance No. 4366 Page 1 August 15, 1990 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Section 2. AMENDMENTS. Auburn City Code Section 15.32.010 entitled "Section 10.308 - amended - Automatic Sprinkler Systems "contained in Chapter 15.36 entitled "Fire Code" is hereby amended as follows: 15.36.035 SECTION 10.30((6))6 AMENDED - AUTOMATIC SPRINKLER SYSTEMS. "AUTOMATIC SPRINKLER FIRE EXTINGUISHING SYSTEMS Section 10.30((6))6(a) ((General)) Automatic ((Sprinkler)) Fire Extinguishing Systems shall be provided in accordance with the provisions of this section. For special provisions on hazardous chemicals and magnesium, and calcium carbide, see 1988 Uniform Fire Code Sections 10.301 and 45.209 and Articles 48, 49 and 80. (b) where required, Automatic ((Sprinkler)) Fire Extinguishing Systems shall be installed and maintained in operable condition as specified in this article in the following locations: 1. All Occupancies Except Group R, Division 3 and Group M 1 and 2. A. All occupancies having over 1((2))0,000 square feet of floor area or more than 40 feet in height or requiring more than 2000 gallons per minute fire flow. B. In every story or basement of all buildings when the floor area exceeds 1500 square feet and there is not provided at least 20 square feet of opening entirely above the adjoining ground level in each 50 lineal feet or fraction thereof of exterior wall in the story or basement on at least one side of the building. Openings shall have a minimum dimension of not less than 30 inches. Such openings shall be accessible to the fire department from the exterior and shall not be obstructed in a manner that firefighting or rescue cannot be accomplished from the exterior. When openings in a story are provided on only one side and the opposite ------------------- Ordinance No. 4366 Page 2 August 15, 1990 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 wall of such story is more than 75 feet from such openings, the story shall be provided with an approved automatic sprinkler system, or openings as specified above shall be provided on at least two sides of an exterior wall of the story. If any portion of a basement is located more than 75 feet from openings required in this section, the basement shall be provided with an approved automatic sprinkler system. C. At the top of rubbish and linen chutes and in their terminal rooms. Chutes extending through three or more floors shall have additional sprinkler heads installed within such chutes at alternate floors. Sprinkler heads shall be accessible for servicing. D. In rooms where nitrate film is stored or handled. E. In protected combustible fiber storage vaults as defined in the Uniform Fire Code. 2. Group A Occupancies. A. When the occupancy has more than 8,000 square feet of gross floor area. B. Nightclubs, discos. An automatic sprinkler system shall be installed in rooms primarily used for entertaining occupants who are ( (drink4:mg) ) consuming alcoholic or non- alcoholic beverages or dining and unseparated accessory uses where the total area of such unseparated rooms and assembly uses exceeds 5000 square feet. For uses to be considered as separated; the separation shall be not less than as required for a one -hour occupancy separation. The area of other uses shall be included unless separated by at least a one -hour occupancy separation. C. Basements. An automatic sprinkler system shall be installed in basements classified as a Group A Occupancy when the basement is larger than 1500 square feet in floor area. ((B--E�l�lbi��e�9-a3gel-Bispla�*s-Reexts---An-at�tematie 9p��ni�le�-system-shall-be-�r�stal led-in-6�e�tp A-6eet�peneies-wl�iel°i-1°ia�*e-mere-than-1�-699 ------------------- Ordinance No. 4366 Page 3 August 15, 1990 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 selxa�e-€eat-ef -f lees-area-tal��el�-can-be-used €er-e�h�b�tlen-ems-display-ptt�peses-)) ((E-))D. Stairs. An automatic sprinkler system shall be installed in enclosed usable space below or over a stairway in Group A, Divisions 2, 2.1, 3 and 4 Occupancies. ((F-))E. Other Areas. An automatic sprinkler system shall be installed under the roof and gridiron, in the tie and fly galleries and in all places behind the proscenium wall of stages; over and within permanent platforms in excess of 500 square feet in area; and in dressing rooms, workshops and storerooms accessory to such stages or permanent platforms. EXCEPTIONS: 1. Stages or platforms open to the auditorium room on three or more sides. 2. Altars, pulpits or similar platforms and their accessory rooms. 3. Stage gridirons when side -wall sprinklers with 135°F rated heads with heat baffle plates are installed around the entire perimeter of the stage except for the proscenium opening at points not more than 30 inches below the gridiron nor more than 6 inches below the baffle plate. 4. Under stage or under platform areas less than 4 feet in clear height used exclusively for chair or table storage and lined on the inside with materials approved for one -hour fire - resistive construction. 3. Group B, Division 2 Occupancies. ( (A--B�ln3e3r�g-anal-dying-establiskments-ka*aing-a €leer-area-a€-8;999-se�a�e-€eat-er-mere-)) ((B-))A. An automatic sprinkler system shall be installed in ((retail-sales-reams-elassed as)) Group B, Division 2 retail sales more than three stories. "Story" for the purposes of this Ordinance shall mean a floor level within the surrounding exterior wall, including basements and mezzanines. ((eeeupaneles-where-the-€leer-area-exeeeds li;e6A-se�a�e-€eat-ems-all-€lees-e�-l�-6�et�p ------------------- Ordinance No. 4366 Page 4 August 15, 1990 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 B--Hivisien-�-retail-saes-eeeupameies-mere than-three-steries-in-height---The-area-e€ messamines-shall-be-imeluded-in-determimimg the -areas -where -sprinklers -are -required.-)) 4. Group E Occupancies. A. Basements. An automatic sprinkler system shall be installed in basements classified as a Group E Occupancy when the basement is larger than 1500 square feet in floor area. B. Stairs. An automatic sprinkler system shall be installed in enclosed usable space below or over a stairway in Group E Occupancies. 5. Group H Occupancies. ((A--Bivisien-�---Am-autemabie-€ire-extinguishing sps�em-shall-be-imsta��ed-im-6reup-H; Bivisien-l-eeeupameies-}anger-khan-�566 square-€eat-im-€leer-area.-)) ((B-))A. Division 2. An automatic fire -extinguishing system shall be installed in Group H, Division 1, 2, 3 and 7 Occupancies ((emeeedimg-1560-square-feet-in-area)). An automatic fire -extinguishing system shall be installed in rooms of Group H, Division 2 Occupancies when flammable or combustible liquids are stored or handled in excess of the quantities set forth in Table No. 9-A of the Building Code, or any combination of flammable liquids exceeds 240 gallons. An automatic fire -extinguishing system shall be installed in paint spray booths or rooms. ((B--Bivisiem-3---Am-autema�ie-dire-e��inguishimg system-shai�-be-imsbaiied-im-6reup-H,- Bivisiem-3-9eeupaneies-larger-sham-3;699 square-€eat-im-€deer-area.-)) ((e--Bivisiem-4---An-automatie-€ire-e�timguishing sps�em-shall-be-insta��ed-im-6reup-H; Bivisien-4-6eeupameies-mere-them-emu-sterp-im height..-)) B. Division 4 and 5. An automatic fire - extinguishing system shall be installed in Group H, Division 4 and 5 occupancies larger than 3000 square feet in floor area. ((E-))C. Division 6. An automatic fire -extinguishing system shall be installed throughout buildings containing Group H, Division 6 ------------------- Ordinance No. 4366 Page 5 August 15, 1990 1 2 3 4 1 LOCATION 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 occupancies. The design of the sprinkler system shall be not less than that required under U.B.C. Standard No. 38-1 for the occupancy hazard classifications as follows: Fabrication Areas Service Corridors Storage Rooms Without Dispensing Storage Rooms With Dispensing Exit Corridors OCCUPANCY HAZARD CLASSIFICATION Ordinary Hazard Group 3 Ordinary Hazard Group 3 Ordinary Hazard Group 3 Extra Hazard Group 2 Ordinary Hazard Group 31 6. Group I Occupancies A. An automatic sprinkler system shall be installed in Group I Occupancies. EXCEPTIONS: �es��}et}tee-anal-��-ene-hett� eenst�t�et}en; -the-at�te2natie-spy}n3�}ems spste7n-xta�*-be-em}��eel-€gem-epe�at}�g- ele}}�e�p; -easel}ae--�£-may-anal-}ntens}tee ease-�ee�ts-anal-patient-s}eep}ng-�eex�s net-exeeeel4:ng-456-seluare-€eet-4:n-area when-eaeh-sueh-ream-is-provided-with smoke-deteeters-eenneeted-te-a een�}nt�etts}y-at�eneleel-staff}en-ems }eea��en-�*thin-the-bt��}d}ng---}neweases €ems-area-and-he}gh�-speei€feel-gin See��ens-596fe}-anal-56�-she}}-net-app}y when-this-exeept}en-}s-useel-)) In jails, prisons and reformatories, the piping system may be dry, provided a manually operated valve is installed at a continuously monitored location. 1 When the design area corridor protected by number of sprinklers, ------------------- Ordinance No. 4366 Page 6 August 15, 1990 of the sprinkler system consists of a one row of sprinklers, the maximum that need be calculated is 13 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Opening of the valve will cause the piping system to be charged. Sprinkler heads in such systems shall be equipped with fusible elements or the system shall be designated as required for deluge systems in U.B.C. Standard No. 38-1. 7. Group R-1 Occupancies. A. When the occupancy has over ((0899-square feet-a€-fleer-area)) 4 units or has over 5000 square feet of floor area or has more than two stories (as defined in Section 3.A. above for Group B, Division 2 Occupancies) within the surrounding exterior walls. B. Ouick response standard sprinkler heads shall be used in accordance with their approved listing in the dwelling units and quest room portions of the building. C. All condominiums shall have the following wording in the recorded Declaration of Covenants and a copy of the document.shall be provided to the Fire Chief or his designee: 1. In the event that any unit should be equipped with a fire sprinkler system, nothing shall be hung from the sprinklers compromising a part of the system nor shall any such sprinklers be painted, covered, or otherwise changed, tampered with or altered. 2. Prior to any alteration, amendment, modification or change thereof, the owners or their agents will submit such alteration, modification or change to the City for approval. 3. The owner and/or agent agrees to comply with all applicable sprinkler requirements including periodic prearranged inspection of any sprinkler system. (B--Ala�n9---Wlgen-9e��i�g-mere-thaw-�96-9p��n#1e�9- a�temat�e-9pr�nk�e�-sp9tems-9ha��-be-9�pe��ised-bp an-app�e�ed-eent�al--p�ep�ieta�p-e�-�emete-stet�en se��iee-e�-a-�eeal-alarm-wk�eh-will-give-an ------------------- Ordinance No. 4366 Page 7 August 15, 1990 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 a�dib�e-s�gna�-at-a-eens�en��y-attended 8. Sprinkler Svstem Supervision Alarms. Automatic sprinkler systems shall be supervised by an approved central, proprietary or remote station service or a local alarm which will give an audible signal at a constantly attended location when the number of sprinklers is: 1. 20 or more in Group I, Division 1 Occupancies. 2. 100 or more in other occupancies. 9. Permissible Omissions. Subject to the approval of the Building Official with the concurrence of the Chief of the Fire Department, sprinklers may be omitted in rooms or areas as follows: A. Where sprinklers are considered undesirable because of the nature of the contents or in rooms or areas which are of non-combustible construction with wholly noncombustible contents and which are not exposed by other areas. Sprinklers shall not be omitted from any room merely because it is damp or of fire resistive construction. B. Sprinklers shall not be installed where the application of water or flame and water to the contents may constitute a serious life or fire hazard, as in the manufacture or storage of, including but not limited to, quantities of aluminum powder, calcium carbide, calcium phosphide, metallic sodium and potassium, quicklime, magnesium powder and sodium peroxide. C. Safe deposit or other vaults of fire resistive construction, when used for the storage of records, files and other documents when stored in metal cabinets. D. Communication equipment areas under the exclusive control of public communication utility agency, provided: 1. The equipment areas are separated from the remainder of the building by one hour fire resistive occupancy separation; and ------------------- Ordinance No. 4366 Page 8 August 15, 1990 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 2. Such areas are used exclusively for such equipment; and 3. An approved automatic smoke detection system is installed in such areas and is supervised by an approved central, proprietary or remote station service, or a local alarm which will give an audible signal at a constantly attended location; and 4. Other approved fire protection equipment, such as portable fire extinguishers or Class II standpipes, is installed in such areas. E. Other approved automatic fire extinguishing systems may be installed to protect special hazards or occupancies in lieu of automatic sprinklers. 10. Area Separation Walls. For the purpose of this Ordinance, ((eaeh-perlen-a€-a-bt�lleling-separaeel bp-one-er-mere-area-separa�len-walls-inay-be eenslelereel-a-separate-bttlleling--pre�leleel-the-area separa�len-walls-meek-the-€ellewing requ4:rement9r)) area separation walls as noted in the 1988 Uniform Buildina Code. Section 505 (e), shall not be considered to separate a building to enable the deletion of the required fire sprinkler system. ((A7-All-area-separat4:on-walls-shall-be-net-less khan-€et�r-hear-€ire-resis�l�re-eenshrt�e�len- �he-�e�al-wlel�h-e€-all-openings-in-st�eh-walls shall-net-emeeed-25-pereent-e€-the-length-e€ the-wall-4:n-eaeh-s€err7--All-5ueh-epenings shall-be-preteeted-by-a-fire-assembip-having a-three-hear-€ire-preteetlen-rating---Ne epenings-shall-be-perm4-tted7)) ( (B--�4rea-separa�len-walls-shall-e��enel-€rein-€he €et�nela�#en-�e-a-peln�-a�-leash-3A-inehes abeve-the-rlee€-) ) 11. Floor area. For the purposes of this ordinance, floor area shall include the total floor area within the surrounding exterior walls on all floor levels including basements and mezzanines. ------------------- Ordinance No. 4366 Page 9 August 15, 1990 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Section 4. The Mayor is hereby authorized to implement such administrative procedures as may be necessary to carry out the directions of this legislation. Section 5. This Ordinance shall take effect and be in force five days from and after its passage, approval and publication as provided by law. INTRODUCED• Zce2 " /7' / V PASSED: z2' / Z' 2�_I) APPROVED • L6�, / / ' / d //t M A 1 O R ATTEST: 0 , '/ )aLj�a 74-0 `Robin Wohlhueter, City Clerk APPROVED AS TO FORM: City AttoTney h PUBLISHED: / (/ ------------------- Ordinance No. 4366 Page 11 August 15, 1990 STATE OF WASHINGTON) ) ss. COUNTY OF KING ) I, Robin Wohlhueter,-the duly appointed, qualified City Clerk of the City of Auburn, a Municipal Corporation and Code City, situate in the County of King". State of Washington, do hereby certify that the foregoing is a full, true'and correct copy of. Ordinance No. 4366 of the ordinances of the City of Auburn, entitled "AN ORDINANCE." Lcertify that said Ordinance No. 4366 was duly passed by the Council and 1 appr6ved by the Mayor of the said City of Auburn, on the the 17th day of December ",A.D:;, 1990. I further certify"that said Ordinance No. 4366 was published as provided by law in the Valley Daily News, a daily newspaper published in the City of Auburn, and of general circulation therein, on the 23rd day of December, A.D., 1990. Witness .my hand and the official seal of the City of Auburn this December 28 '1990 > A.D. Robin Wohlhueter;'� City Clerk" City of Auburn_ 25 West Main, Auburn, WA 98001-4998 (206) 931-3000