Loading...
HomeMy WebLinkAboutRevision 4_010414 Complete.pdfDIVISION 9: MATERIALS Revised 12/2013 Engineering Construction Standards 9-33 Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Division 9 (12-13) Clean.doc 9-29.26 TRAFFIC SIGNAL BATTERY BACKUP SYSTEM New Section All traffic signal battery back-up power units shall employ a 24 Volt DC battery system. 12 and 48 Volt battery configurations will not be accepted. All battery backup power units shall utilize the Dimensions Inverter/Charger unit, complete with associated remote control display panel. Batteries shall be connected utilizing approved quick-connect modular battery connectors. Battery connection scheme must provide a “Hot-Swap” capability during operation. Battery cable sizing shall be appropriate for the type and quantity of batteries supplied. Batteries shall be 12 Volts DC, 100 Amp Hour minimum, Absorbed Glass Mat type, Group 27. Batteries shall meet or exceed Specification MIL B-8565J (Sec 4.6.22). The quantity of batteries to be supplied shall be four batteries. All battery backup power units shall possess an AC voltage bypass/disconnect switch or relay. The bypass/disconnect method shall couple the normal AC power source directly to the signal controller cabinet, while completely isolating the inverter/charger unit from the circuit. All battery backup power units shall possess a 0-4 hour Time Delay Relay, with both “delay on make” and “delay on break” contact sets. This relay shall be energized upon loss of AC input power, or “Inverter On” condition. Relay contacts must be easily accessible, and clearly labeled. Cabinets shall be equipped with thermostatically controlled fan ventilation. Equipment supplied shall be the pre-approved model listed below, or approved equal. Manufacturer/Vendor Model/Type Rhino(Brownfield) Manufacturing, Inc. BMI-7000 Traffic Light Backup Power Unit Installation/Cabinet Mounting Style: Traffic UPS Cabinets shall not exceed 30 inches in width and 18 inches in depth. Cabinet height shall be sufficient to accommodate the quantity of batteries required by the contract, or specified by the project engineer. Installation shall be performed in accordance with City of Auburn Construction Standards. DIVISION 9: MATERIALS Revised 12/2013 Engineering Construction Standards 9-34 Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Division 9 (12-13) Clean.doc 9-30 WATER DISTRIBUTION MATERIALS 9-30.1(1) DUCTILE IRON PIPE Supplement All ductile iron pipe used on this project shall be “Special Class 52”, except pipe to be joined using bolted flange joints shall be “Special Class 53”. 9-30.2(1) DUCTILE IRON PIPE Supplement All pipe fittings, adapters and joints for ductile iron pipe shall be ductile iron designed to AWWA Specification (unless otherwise approved in writing by the Engineer) with sufficient tangent at the ends to allow for proper joint connections and shall be coated to give protection to them equal to that given the pipe. Field fabrication fittings will not be permitted. Flexible couplings shall be of the style as required for specific application. 9-30.2(6) RESTRAINED JOINTS Supplement Restrained joint (R.J.) pipe and fittings, where shown on the Plans, shall be suitable for 350 psi working pressures and be US Pipe TR Flex or American Pipe Flex-Ring. Pipe manufacturer restrained joints using exposed bolts in the thrust restraint assembly and restraining systems using set screws, anchor lugs, wedges, or other friction devices will not be considered equal to the systems listed. All welding associated with the restraint system shall be performed in the pipe manufacturer’s shop. No field welding will be permitted. 9-30.3(1) GATE VALVES (3-inches to 16-inches) Replacement Resilient wedge gate valves shall be used on all 12” and smaller water lines and shall be manufactured by Clow, American Darling, Waterous, Dresser M & H or Mueller with epoxy- coated valve interiors. The valves shall conform to ANSI/AWWA Specifications C-509 with a 200-psi working pressure rating. They shall be iron bodied, bronze-mounted, non-rising stem and counterclockwise opening with a 2 inch square operating nut. All valves on the fire hydrant line(s) shall be 6-inch diameter mechanical joint by flange. All other valves shall be either mechanical joint by flange or Mechanical joint shackled to tees or crosses. Valve stems shall be provided with O-ring seals. 9-30.3(3) BUTTERFLY VALVES Supplement Butterfly valves conforming to AWWA Specification C-504, Class 150 B shall be used on all 14 inch and larger water mains. They shall have Mechanical joint ends and be rated at 150 psi working pressure. Operator shall have standard AWWA 2 inch square nut. 9-30.3(4) VALVE BOXES Supplement Valve boxes shall be two-piece, adjustable, cast-iron (with additional extension pieces, if necessary), as manufactured by the Olympic Foundry Company, or equal, with a minimum DIVISION 9: MATERIALS Revised 12/2013 Engineering Construction Standards 9-35 Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Division 9 (12-13) Clean.doc inside diameter of 5 inch. The word “WATER” shall be cast in relief on the top of all valve box covers. In addition, the letters “NC” shall be cast in place on valve box covers for those valves that are normally closed. Valve box covers shall be of a design and thickness so traffic will not allow them to be flipped out. 9-30.3(8) TAPPING SLEEVE AND VALVE ASSEMBLY Supplement Tapping sleeves and valves shall conform to the following: 1. For wet taps on mains 12 inch diameter and larger or size-on-size, the tapping sleeve shall be the full M.J. type, cast-iron, twin seal as manufactured by Mueller, Tyler, Taylor, M & H, or epoxy-coated fabricated-steel, as manufactured by JCM, Rockwell or equal; 2. For wet taps on mains 10 inch diameter and smaller, or at least 2 inch diameter smaller than the main size, the tapping sleeve shall be the wraparound style, stainless steel or epoxy-coated fabricated-steel, or cast-iron M.J. as manufactured by Romac, Ford, M & H, Rockwell, Smith Blair, or equal. 9-30.5 HYDRANTS Supplement Fire hydrants shall have two 2½-inch hose ports (National Standard Thread) and one 4½-inch pumper port (National Standard Thread) with caps and no chains, 1¼ inch pentagonal operating nut (counterclockwise) opening, O-ring-type stuffing box, automatic barrel drain, and 5¼ inch valve opening. Hydrants shall be equipped with a 5” Storz adapter with blind cap, or approved equal, where required by the Fire Department. Hydrants shall conform to the latest revision of AWWA Standard Specification No. C-502 for dry-barrel fire hydrants for ordinary water service. Hydrants shall be Mueller “Centurion” #A-423, M & H Style 929 Resilient (Brass-to-Brass Seats), or American AVK 2780. 9-30.6 WATER SERVICE CONNECTIONS (2-INCHES & SMALLER) Revision All water service materials shall be low lead brass CDA 89833 or CDA 89520, and shall meet ANSI/AWWA C800 and NSF 61 Annex G maximum lead requirements. 9-30.6(1) SADDLES Replacement Saddles for 1½ inch and 2 inch pipe taps shall be epoxy-coated ductile iron, with double stainless steel straps and cemented in place neoprene gaskets. Saddles shall have I.P.S. female threads. 9-30.6(2) CORPORATION STOPS Supplement 1½ inch and 2 inch corporation stops shall be installed with saddle at the pipe main. The 1½ inch and 2 inch corporation stops shall be Mueller B-25028N, Ford FB1100-Q-NL, or DIVISION 9: MATERIALS Revised 12/2013 Engineering Construction Standards 9-36 Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Division 9 (12-13) Clean.doc approved equal with M. I. P. threaded inlets and outlets with a compression connection suitable for connecting to Type K copper tubing per Section 9-30.6(3)A (Copper Tubing). ¾ inch and 1 inch corporation stop inlets shall have tapered tapping threads per AWWA-C800 for insertion directly into the pipe main, and the outlets shall have a compression connection suitable for connecting to Type K copper tubing per Section 9-30.6(3)A (Copper Tubing). Corporation stops shall be Mueller B-25008N, Ford FB1000-Q-NL, or approved equal. 9-30.6(3) SERVICE PIPES Supplement The City allows Type K copper tubing for all water service connections. For 1 ½-inch to 2- inch high density polyethylene (HPDE) SDR-9 (in copper tube size) with stainless steel liners in all couplings and wrapped with a #10 insulated copper tracer wire is acceptable. All connections to copper tubing or polyethylene will be with Mueller 110 Compression Connections or approved equal unless otherwise specified. 9-30.6(5) METER SETTERS (Meter Yokes) Replacement Meter yokes shall conform to the following: A. 1½ inch & 2 inch inlet and outlet legs have multi-purpose threaded ends with a Mueller H-15428N or approved equal M. I. P. thread by compression connection straight coupling suitable for connecting to Type K copper tubing per Section 9- 30.6(3)A (Copper Tubing) on the outlet; 1 inch inlet and outlet legs have compression connection suitable for connecting to Type K copper tubing per Section 9-30.6(3)A (Copper Tubing) on the outlet; B. They shall be equipped with a brace pipe eye; C. Dimensions; height from centerline of inlet/outlet pipe to the centerline of meter inlet/outlet. 1. 1 inch yokes = 10 inch high; 2. 1 ½ inch yokes = 12 inch min. high; 3. 2 inch yokes = 12 inch min. high; D. All yokes shall come equipped with angle stops per Section 9-30.6(5)A (Meter Stops) located at the meter inlet connection and check valves per Section 9-30.6(5)B (Meter Check Valves) located at the meter outlet connection. Meter yokes shall be equal to the following: 1. 1 inch service; yokes shall be Mueller B-2470-2N, Ford VBHH-70-10W-Q-NL or approved equal; 2. 1 ½ inch and 2 inch service; yokes shall be Mueller B-2423-2N, Ford VBHH- 70-12BCH-NL, or approved equal; DIVISION 9: MATERIALS Revised 12/2013 Engineering Construction Standards 9-37 Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Division 9 (12-13) Clean.doc 9-30.6(5)A METER STOPS New Section Meter stops shall be angle-type with locking wing equal to the following: A. ¾ inch and 1 inch service; stop shall be Mueller B-24265; B. 1½ inch and 2 inch service; stop shall be Mueller B-24286; 9-30.6(5)B METER CHECK VALVES New Section Meter check valves shall be angle-type equal to the following: A. ¾ inch and 1 inch service; check shall be Mueller H-14244; B. 1½ inch and 2 inch service; check shall be Mueller H-14244 with meter flange; 9-30.6(5)C CURB VALVES New Section Curb valves shall be straight ball-type equal to the following: A. 1½ inch and 2 inch service; curb valves shall be Mueller B-25170N, Ford B41-W-Q- NL, or approved equal with M. I. P. thread by compression connection straight coupling suitable for connecting to Type K copper tubing per Section 9-30.6(3)A (Copper Tubing) on the inlet; B. 1-inch service; curb valves shall be Mueller B-25146N, Ford B44-W-Q-NL, or approved equal with compression connection straight coupling suitable for connecting to Type K copper tubing per Section 9-30.6(3)A (Copper tubing); C. Locate curb valves in the meter boxes where possible and 1 foot outside the meter boxes where the inside room is not available. 9-30.6(7) METER BOXES Supplement Meter boxes shall be the following: A. Boxes for 1 inch meters shall be Raven RMB-13x24x12 or Mid-States Plastics BCF Series MSBCF-1324-12. Lids shall be ductile or cast iron with 2-inch AMR port. Traffic rated cover shall be used in areas of vehicular traffic or as required by the Engineer; B. Boxes for 1½ inch and 2 inch meters shall be Raven RMB-17x30x12 or Mid-States Plastics MSBBCF-1730-12. Lids shall be ductile or cast iron reader with 2- inch AMR port. Traffic rated cover shall be used in areas of vehicular traffic or as required by the Engineer. DIVISION 9: MATERIALS Revised 12/2013 Engineering Construction Standards 9-38 Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Division 9 (12-13) Clean.doc 9-36 FILTER FABRIC 9-36.1 FILTER FABRIC FOR INFILTRATION SYSTEMS New Section Filter fabric for permanent infiltration systems shall be a non-woven polypropylene geotextile fabric, Contech C45-NW as manufactured by Contech Construction Products Inc., or equivalent. END OF DIVISION 9 SECTION II: STANDARD DETAILS TABLE OF CONTENTS Revised 12/2013 ........................... City of Auburn Engineering Construction Standards ...................... iii Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Section II Table Of Contents (12-13).doc STANDARD DETAIL NAME STANDARD DETAIL NUMBER STORM DRAINAGE FLOW RESTRICTOR (TEE) ...........................................................................................................................STORM-01 MULTIPLE ORIFICE CONTROL STRUCTURE ............................................................................................STORM-02 SMALL SITE, WATER QUALITY CONTROL STRUCTURE ........................................................................STORM-03 GRADING/EROSION DISCHARGE CONTROL STRUCTURE ......................................................................STORM-04 RESIDENTIAL INFILTRATION TRENCH SYSTEM FOR DOWN SPOUTS .................................................STORM-05 RESIDENTIAL INFILTRATION DRY WELL DETAIL ...................................................................................STORM-06 RESIDENTIAL FOOTING DRAIN DETAIL....................................................................................................STORM-07 HEADWALL WITH GRATE ...........................................................................................................................STORM-08 THROUGH-CURB INLET FRAME & GRATE WITH VERTICAL CURB INSTALLATION ..........................STORM-09 THROUGH-CURB INLET FRAME ................................................................................................................STORM-10 CURB & GUTTER REINFORCING DETAIL..................................................................................................STORM-11 RESIDENTIAL SIDEWALK DRAIN ...............................................................................................................STORM-12 WATER WATER MAIN BLOCKING ...........................................................................................................................WATER-01 TYPICAL AIR & VACUUM RELIEF VALVE DETAIL ..................................................................................WATER-02 2” PERMANENT BLOW OFF ASSEMBLY DETAIL .....................................................................................WATER-03 TEMPORARY BLOW OFF DETAIL ..............................................................................................................WATER-04 DOUBLE DETECTOR CHECK VALVE ASSEMBLY AND VAULT (Page 1 of 2).........................................WATER-05 DOUBLE DETECTOR CHECK VALVE ASSEMBLY AND VAULT (Page 2 of 2).........................................WATER-05a IRRIGATION FROM DOMESTIC SERVICE LINE WITH D.C.V.A. UP TO 2” ..............................................WATER-06 5 ¼” M.V.O. HYDRANT SETTING DETAIL .................................................................................................WATER-07 FIRE HYDRANT LOCATION IN CUT OR FILL WITH GUARD POSTS DETAIL .........................................WATER-08 ¾” TO 3” FIRE SPRINKLER LINES WITH DOMESTIC SERVICE LINE ......................................................WATER-09 PRESSURE REDUCING VALVE STATION FOR 8” DIA. WATERLINE (Sheet 1 of 3) .................................WATER-10 PRESSURE REDUCING VALVE STATION FOR 8” DIA. WATERLINE (Sheet 2 of 3) .................................WATER-10a PRESSURE REDUCING VALVE STATION FOR 8” DIA. WATERLINE (Sheet 3 of 3) .................................WATER-10b PRESSURE REDUCING VALVE STATION FOR 10” DIA. WATERLINE (Sheet 1 of 3) ...............................WATER-11 PRESSURE REDUCING VALVE STATION FOR 10” DIA. WATERLINE (Sheet 2 of 3) ...............................WATER-11a PRESSURE REDUCING VALVE STATION FOR 10” DIA. WATERLINE (Sheet 3 of 3) ...............................WATER-11b PRESSURE REDUCING VALVE STATION FOR 12” DIA WATERLINE (Sheet 1 of 3) ................................WATER-12 PRESSURE REDUCING VALVE STATION FOR 12” DIA. WATERLINE (Sheet 2 of 3) ...............................WATER-12a PRESSURE REDUCING VALVE STATION FOR 12” DIA. WATERLINE (Sheet 3 of 3) ...............................WATER-12b ¾” & 1” WATER METER AND SERVICE LINE INSTALLATION ................................................................WATER-13 1 ½” & 2” WATER METER AND SERVICE LINE INSTALLATION .............................................................WATER-14 NOT USED ......................................................................................................................................................WATER-15 WATER METER LOCATION AND SERVICE LINE MATERIAL SCHEDULE .............................................WATER-16 3” OR 4” WATER METER AND SERVICE LINE INSTALLATION (Sheet 1 of 2) .........................................WATER-17 3” OR 4” WATER METER AND SERVICE LINE INSTALLATION (Sheet 2 of 2) .........................................WATER-17a VALVE WRENCH EXTENSION BOX ...........................................................................................................WATER-18 C.I. 18” VALVE BOX TOP AND VALVE BOX COVER ................................................................................WATER-18a 5” C.I. SOIL PIPE VALVE BOX EXTENSION AND C.I. VALVE BOX BOTTOM ........................................WATER-18b NON-SINGLE FAMILY SERVICE LINES WITH DEDUCT METER..............................................................WATER-19 TEMPORARY COMBINATION HYDRANT METER/REDUCED PRESSURE BACKFLOW ASSY .............WATER-20 REDUCED PRESSURE BACKFLOW ASSEMBLY (OUTSIDE INSTALLATION) ........................................WATER-21 REDUCED PRESSURE BACKFLOW ASSEMBLY (INSIDE INSTALLATION) ............................................WATER-22 DOUBLE CHECK VALVE ASSEMBLY (OUTSIDE INSTALLATION) .........................................................WATER-23 DOUBLE CHECK VALVE ASSEMBLY (INSIDE INSTALLATION) .............................................................WATER-24 SECTION II: STANDARD DETAILS TABLE OF CONTENTS Revised 12/2013 ........................... City of Auburn Engineering Construction Standards ...................... iv Ref.: H:\Engineering Standards Manuals\02 Construction Standards\02-3 Current Working Files\2.3.3 Revisions in Progress\Section II Table Of Contents (12-13).doc STANDARD PLAN NAME STANDARD PLAN NUMBER WSDOT STANDARD PLANS (COMMONLY USED BY CITY OF AUBURN AND NOT INCLUDED HEREIN) CEMENT CONCRETE PAVEMENT JOINTS .......................................................................................... A-40.10-00 CATCH BASIN TYPE 1 ............................................................................................................................ B-05.20-00 CATCH BASIN TYPE 1L ......................................................................................................................... B-05.40-00 CATCH BASIN TYPE 1P (For PARKING LOT) ....................................................................................... B-05.60-00 CATCH BASIN TYPE 2 ............................................................................................................................ B-10.20-00 CATCH BASIN TYPE 2 WITH BAFFLE TYPE FLOW RESTRICTOR..................................................... B-10.60-00 MANHOLE TYPE 1 .................................................................................................................................. B-15.20-00 MANHOLE TYPE 2 .................................................................................................................................. B-15.40-00 MANHOLE TYPE 3 .................................................................................................................................. B-15.60-00 CONCRETE INLET .................................................................................................................................. B-25.60-00 RECTANGULAR FRAME (REVERSIBLE) .............................................................................................. B-30.50.00 RECTANGULAR SOLID METAL COVER ............................................................................................... B-30.20.01 RECTANGULAR VANED GRATE........................................................................................................... B-30.30-00 RECTANGULAR HERRINGBONE GRATE ............................................................................................. B-30.50-00 MISCELLANEOUS DETAILS FOR DRAINAGE STRUCTURES ............................................................. B-30.90-01 CONCRETE THRUST BLOCK FOR CONVEX VERTICAL BENDS ...................................................... B-90.50-00 DROP CONNECTIONS FOR SANITARY SEWER USE........................................................................... B-85.50-01 BEAM GUARDRAIL: TYPES 1 ~ 4 (W-Beam) ..................................................................................................... C-1 REINFORCED CONCRETE RETIANING WALL TYPE 1 AND 1SW ...................................................... D-10.10-01 REINFORCED CONCRETE RETAINING WALL TYPE 2 AND 2SW ...................................................... D-10.15-01 CEMENT CONCRETE CURBS ................................................................................................................. F-10.12-00 EXTRUDED CURB ................................................................................................................................... F-10.42-00 PRECAST CONCRETE SLOPED MOUNTABLE CURB ........................................................................... F-10.62-01 PRECAST CONCRETE DUAL FACED SLOPED MOUNTABLE CURB .................................................. F-10.64-02 SIGNAL STANDARD TYPE DESIGNATIONS AND TYPES PPB, PS, I, RM AND FB DETAILS ...................... J-7a TYPE 3 INDUCTION LOOP ................................................................................................................................ J-8c LOCKING LID STANDARD JUNCTION BOX TYPES 1 & 2 ................................................................... J-40.10-00 PULL BOX ................................................................................................................................................ J-90.10-00 CABLE VAULT ......................................................................................................................................... J-90.20-00 ROAD CLOSURE, WITH DIVERSION..................................................................................................... K-10.20-01 ROAD CLOSURE, WITH OFF-SITE DETOUR ........................................................................................ K-10.40-00 LANE CLOSURE, WITHOUT FLAGGERS ~ LOW VOLUME ROAD ..................................................... K-20.20-01 LANE CLOSURE, WITH FLAGGER CONTROL ..................................................................................... K-20.40-00 LANE CLOSURE, WITH PILOT CAR ...................................................................................................... K-20.60-00 LANE SHIFT, ONTO PASSING LANE ..................................................................................................... K-22.20-01 SINGLE LANE CLOSURE, WITH ENCROACHMENT ............................................................................ K-24.20-00 DOUBLE LANE CLOSURE, ON MULTILANE ROADWAY ................................................................... K-24.40-01 SINGLE LANE CLOSURE, ON MULTILANE ROADWAY ..................................................................... K-24.60-00 SINGLE LANE CLOSURE, WITH TEMPORARY CONCRETE BARRIER .............................................. K-24.80-01 LANE SHIFT, ONTO TWO-WAY LEFT TURN LANE ............................................................................. K-26.20-00 LEFT AND CENTER LANE CLOSURE ~ TWO-WAY LEFT TURN LANE ............................................. K-26.40-01 INTERSECTION ~ LANE SHIFT ON THREE LANE TWO-WAY LEFT TURN LANE ............................ K-30.20-00 INTERSECTION ~ LANE SHIFT ON FIVE LANE TWO-WAY LEFT TURN LANE ................................ K-30.40.01 INTERSECTION ~ RIGHT LANE CLOSURE, FAR SIDE ........................................................................ K-32.20-00 INTERSECTION ~ LEFT LANE CLOSURE, FAR SIDE ........................................................................... K-32.40-00 INTERSECTION ~ MULTIPLE LANE CLOSURE .................................................................................... K-32.60-00 INTERSECTION ~ HALF ROAD CLOSURE WITH LANE SHIFT ........................................................... K-32.80-00 INTERSECTION ~ PEDESTRIAN DETOUR ............................................................................................ K-34.20-00 INTERSECTION ~ SHOULDER WORK................................................................................................... K-36.20-00 SHOULDER CLOSURE ~ HIGH SPEED ROADWAY (45 MPH OR HIGHER) ........................................ K-40.20-00 SHOULDER CLOSURE ~ LOW SPEED ROADWAY (40 MPH OR LESS) .............................................. K-40.40-00 SHOULDER CLOSURE ~ SHORT DURATION ....................................................................................... K-40.60-00 WORK BEYOND THE SHOULDER ........................................................................................................ K-40.80-00 EMERGENCY ~ PASSABLE HAZARD ................................................................................................... K-55.20-00 SPEED ZONE, SUPPLEMENTAL SIGNING ~ CHIP SEAL PROJECT .................................................... K-60.20-02 MOTORCYCLE, SUPPLEMENTAL SIGNING ......................................................................................... K-60.40-00 TEMPORARY CHANNELIZATION ......................................................................................................... K-70.20-00